GATE AG 2015 • Q55 MCQ • 2 Marks

Section 3: Farm Power

Farm Power

Subtopic: Calculation of power, torque, fuel consumption, heat load and power losses

Question Statement:

In a cascade refrigeration system, the COPs of the cooling cycle and cascade are 3.7 and 4.2, respectively. If tonnage (1 TR = 3.52 kW) of the cooling cycle is 15 and the cascade removes 70% of the total heat rejected in the liquid receiver of the cooling cycle, then the powers required by the cooling and cascade compressors in hp are _____ and _____, respectively.

Options:

  • (A) 67.07, 46.95
  • (B) 52.08, 39.35
  • (C) 19.13, 14.99
  • (D) 14.27, 11.18

Official Answer Key:

C

Step-by-Step Solution & Explanation

Cooling-cycle refrigeration load: Q_cool = 15 TR × 3.52 kW/TR = 52.8 kW. Cooling-cycle compressor work: W_cool = Q_cool/COP_cool = 52.8/3.7 = 14.27 kW. Heat rejected by the cooling cycle at the liquid receiver (cascade condenser) = Q_cool + W_cool = 52.8+14.27 = 67.07 kW. Heat absorbed by the cascade evaporator = 70% of this rejected heat = 0.7×67.07 = 46.95 kW. Cascade compressor work: W_cascade = 46.95/COP_cascade = 46.95/4.2 = 11.18 kW. Converting both compressor powers to hp (1 hp = 0.746 kW): W_cool = 14.27/0.746 = 19.13 hp; W_cascade = 11.18/0.746 = 14.99 hp. Matches option (C) exactly. (Note the intermediate kW values 67.07 and 46.95 numerically coincide with the hp figures in distractor option (A) — a trap for candidates who forget the final kW→hp conversion.)

Practice This in Real CBT Exam Interface

Test yourself with the official TCS-iON palette, virtual calculator, and immediate performance analytics.

Launch CBT Mock Test